48v inverter output short circuit and output voltage protection instructions

Column:Industry News Time:2021-10-19
When the inverter output feedback does not have a zero-crossing point for 64ms continuously,

(1) Output short-circuit protection of the inverter

When the inverter output feedback does not have a zero-crossing point for 64ms continuously, it is regarded as an output short circuit, the UPS output is turned off, the UPS beeps for a long time and an alarm is displayed on the panel.

(2) Output voltage protection of the inverter

When the inverter output feedback voltage is lower than 140V or higher than 276V for 80ms continuously, it is regarded as output undervoltage or overvoltage for protection, the UPS transfers to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(3) BUS overvoltage protection of the inverter

When the BUS voltage exceeds 440V for 64ms continuously, it is considered that the BUS is over-voltage and protected, the UPS transfers to the bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel.

(4) Inverter current limiting protection

The protection circuit monitors the output current value. If it exceeds 3.6 times the rated current, the current-limiting protection circuit immediately turns off the PWM and resets the PWM at a 19.2kHz cycle until the output current value is less than 3.6 times the rated current.

(5) Over-temperature protection of the inverter

When the system temperature is too high, the temperature switch trips, making the UPS transfer to bypass mode, the UPS beeps for a long time and an alarm is displayed on the panel (detection time 0.5s).

(6) Load protection of inverter


110%~130%

If the UPS detects that the load exceeds 110% before jumping from the bypass to the inverter, it cannot enter the inverter state. At this time, the UPS beeps once every 0.5s and displays the status on the panel. If the load is detected between 110% and 130% after power-on, the UPS will beep once every 0.5s and display the status on the panel. After 10s, the UPS will switch to bypass mode; after that, if the load is reduced to below 100%, the UPS Restart the soft boot. If the UPS detects that the load is between 110% and 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; if the load is not reduced below 100%, the UPS will transfer to bypass after 10s Mode, this state can only be released by pressing the OFF button.


Greater than 130%

If the load is detected to be greater than 130% after power-on, the UPS will beep once every 0.5s, and the status will be displayed on the panel, and the UPS will transfer to the bypass state. After that, if the load is reduced to below 100%, the UPS restarts. If the UPS detects that the load is greater than 130% in the battery power supply mode, the UPS will beep every 0.5s and display the status on the panel; at the same time, the UPS will switch to bypass mode; this status can only be released by pressing the OFF button.


主站蜘蛛池模板: 欧美三级在线观看视频 | 圣爱天堂网站亚洲欧美 | 国产欧美精品三区 | 久久免费福利 | 99成人国产精品视频 | 免费视频专区一国产盗摄 | 蜜桃臀在线成人亚洲 | 91天堂素人精品系列全集亚洲 | 国产在线91 | 亚洲视频在线观看地址 | 欧美日韩亚 | 污网站免费观看在线高清 | 四虎影视在线看免费完整版 | 爱福利视频 | 很很干很很操 | 日本爽爽爽爽爽爽在线观看免 | 一区二区三区免费高清视频 | 四虎四虎 | 亚洲欧美日本国产综合在线 | 欧美日韩视频在线第一区 | 亚洲欧美视频在线观看 | 免费视频黄 | 黄色网址免费在线观看 | 国产精品国产三级农村妇女 | 日本免费黄色 | 精品国产网 | 91青青草原 | 日韩亚洲一区中文字幕 | 国产午夜精品视频 | 手机看片欧美 | 日本高清在线视频www色下载 | 国产一级片视频 | 在线不卡一区二区 | 一区二区三区四区欧美 | 亚洲国产精品毛片∧v卡在线 | 国产成人91青青草原精品 | 晚上看的www视频高清免费动漫 | 久久精品视频5 | 精品国产欧美一区二区三区成人 | 96久久 | 一区二区色 |